Date Fan Description Status
23-Aug-18 2F06 Turned OFF. Temp reading too low. FAIL
30-Nov-17 2F31 Increase airflow to noise limit as cooling capacity limiting. FAIL
20-Apr-18 2F33 Need to move VENT to room. FAIL
20-Apr-18 2F34 Fan speed turned up. Noisy in meeting room. Balance between cooling and noise. Replace Fan. Encouraged Water Flow. Bled. Bent spindle. Suggest flush and replace CV. FAIL
20-Apr-18 3F10 Vent FAIL
02-Aug-18 3F36 Leak. Put tray underneat. Plumbing issue. Flush FAIL
01-Apr-18 4F16 OFF. FLUSH FAIL
19-Apr-18 4F40 no flow FAIL
23-Aug-18 5F18 Temp sensor fail. FCU turned off. FAIL
20-Apr-18 5F28 Control error fixed. Still no cooling. FAIL
23-Aug-18 5F32 Reports of intermittent noise. FAIL
23-Aug-18 5F33 Too noisy. Turned OFF. Then too hot. Turned ON. Must replace fan. FAIL
Date Fan Description Status
23-Aug-18 2F06 Turned OFF. Temp reading too low. FAIL
27-Oct-17 3F41 Checked valves OK. Open/Close taps. Bled. 23.3 to 25. Weak but OK FAIL
27-Oct-17 3F42A Checked valves OK. Open/Close taps. 25. Weak but OK. FAIL
27-Oct-17 4F10 FCU Blocked? FAIL
27-Oct-17 4F11 FCU Blocked? FAIL
30-Nov-17 4F32 Valve needs replacing. FAIL
13-Nov-17 4F37 No HW Flow. Flush or Taps. FAIL
27-Oct-17 5F06 No flow. FAIL
30-Nov-17 5F16 No heating. FAIL